How the calculation works

Estimated AC fixture current = input watts ÷ (voltage × power factor), or the input current you enter. Available calculated-load budget = breaker amps − 1.25 × other continuous amps − other noncontinuous amps. The fixture count is rounded down after dividing that budget by fixture amps × 1.25 for continuous lighting, or fixture amps for noncontinuous lighting. A supplied manufacturer fixture limit can reduce that count.

This is for identical single-phase AC fixtures on similar branch circuits, including line-to-neutral or line-to-line supplies. It does not design a three-phase distribution system. Circuit estimates assume the same other loads and equipment on each circuit.

Planning estimate only. Inrush current, switching limits, conductor ampacity, voltage drop, temperature, leakage current and local requirements can lower the usable fixture count. An unknown manufacturer limit is not an unlimited allowance. Have the final circuit design checked by a qualified electrician.

How many LED lights can I put on a 20-amp circuit?

The number depends on each fixture’s input current, operating duration, other connected loads, and the LED driver’s starting characteristics.

For continuous lighting on a standard-rated 20-amp circuit, the basic running-load allowance is 16 amps, assuming no other loads. A 150-watt fixture operating at 120 volts with a 0.95 power factor draws approximately 1.32 amps, allowing 12 fixtures by this calculation.

This is a planning estimate. Driver inrush current, wiring conditions, and switching equipment can reduce the usable count. Contact LED Lighting Supply with your fixture selection, supply voltage, and breaker details. Our Product Specialists can help identify the fixture specifications and product-specific limits needed for your electrician’s circuit design.

Does the 80% rule apply to LED lighting circuits?

For typical U.S. branch-circuit planning with standard-rated breakers, continuous loads require additional capacity. A continuous load is one whose maximum current is expected to continue for three hours or more.

If lighting is the only load, this generally means planning around 12 amps on a 15-amp circuit or 16 amps on a 20-amp circuit. Shared circuits require separate consideration of their continuous and noncontinuous loads.

Should I use fixture wattage or input amps to calculate lights per circuit?

Use the fixture’s AC input current at your actual supply voltage when available. Do not substitute the driver’s DC output current.

If input current is unavailable, estimate it using:

Input amps = actual input watts ÷ (supply voltage × power factor)

Use the fixture’s electrical input watts—not its advertised “400-watt metal halide equivalent.” Power factor affects current draw, so dividing watts by volts alone can underestimate the circuit load. Our Product Specialists can help you find the correct input wattage, current, and power factor for the LED lights you are purchasing.

Why can LED lights trip a breaker even when their total wattage is below its capacity?

LED drivers can draw a brief surge of inrush current when switched on. Starting multiple fixtures together may trip a breaker even when their normal operating current fits within its running-load capacity.

Contact LED Lighting Supply for help reviewing the driver specifications and available fixture-per-breaker limits for your selected lights. Provide the fixture model, quantity, supply voltage, breaker details, and how the lights are switched. Your electrician should also verify switch, relay, and lighting-control ratings and investigate repeated tripping. A larger breaker is not a substitute for checking the installation.

Can I run more LED fixtures on a 277-volt circuit than a 120-volt circuit?

Generally, yes. At the same input wattage and similar power factor, a fixture draws less current at 277 volts, potentially allowing more fixtures on a circuit with the same amp rating.

Every fixture must support the supplied voltage. Tell our Product Specialists your project’s voltage and lighting requirements, and we can help you select compatible fixtures and provide their electrical specifications. A calculator can help compare options, while your electrician confirms circuit capacity, wiring, controls, and installation requirements.