40 / 60 / 80 Watt Adjustable Round Explosion Proof LED Light | 6400 to 12800 Lumens | Class 1 Div 2 | 4000K / 5000K / 6500K | 100-277V
This adjustable 40/60/80W fixture suits hazardous-location and paint booth lighting needing 6,400 to 12,800 lumens, selectable color temperature, and 120-degree distribution. UL 844 Class I, II, and III listings support specified hazardous environments, while IP66, NEMA4X, IK08, 10kV surge protection, and -40F to 131F operation address demanding conditions. Surface, yoke, and pendant mounting provide installation flexibility.
15 in stock
Product Specifications
UL Specs
- UL 844 Hazardous Locations
- Class I, Division 2, Groups A, B, C, D
- Class II, Division 1, Groups E, F, G
- Class II, Division 2, Groups F, G
- Class III
- UL 1598 Suitable for Wet Locations
- UL 1598A Marine Outside Type
- ABS
- Vibration 3G
- NEMA4X
- T4A @ Ta 55° C
Key Features
| Brand | LED Lighting Supply |
| Watts | 40 | 60 | 80 |
| Lumens | 6400 | 9600 | 12800 |
| Lumens Per Watt | 160 |
| Replaces | 175 Watt Metal Halide |
| Voltage | 100V-277V |
| Color Temperature | 4000K or 5000K or 6500K |
| CRI | 70+ |
| Dimming | 1-10V |
| Beam Angles (Std) | 120° |
| Optics | Tempered Glass Lens |
| Lifespan | 50,000 (L70) hours |
| Mounting | Surface or Yoke or 3/4 in NPT Pendant |
| Fixture Color | Gray |
| Frequency (Hz) | 50-60Hz |
| Power Factor | >.95 |
| THD | < 10% |
Durable Construction
| Housing | Die-Cast Aluminum |
| IP Rating | IP66 |
| IK Rating | IK08 |
| Surge Protection | 10kV |
| Operating Temperature | -40°F to 131°F |
| Certifications | UL |
| Warranty | 5 years |
Measurements
| Dimensions (in) | 11.22 x 10.39 |
| Weight (lbs) | 14.5 |
| Cord Length | No Cord |
Features/Accessories
- Color Adjustable
- Wattage Adjustable
Product Lighting Layout Estimator
Use this estimator to calculate approximate fixture count, spacing, and average foot-candles for a simple rectangular space using the selected LED fixture. Enter your room dimensions, mounting height, target foot-candles, light loss factor, and room/layout condition to generate a preliminary lighting layout. When IES photometry is available, workplane height and room reflectance controls are shown.
Project Inputs
Estimated Results
Estimated average foot-candles are preliminary and should be verified with a lighting plan for project-critical applications.
Room / Layout Condition: This field is used only when usable IES photometry is not available. In fallback mode, it acts as a simplified room utilization factor for reflectance, fixture distribution, racking, obstructions, and how much fixture light reaches the work area. Open / light-colored spaces use 0.90, typical warehouses or shops use 0.75, racked or obstructed spaces use 0.60, and dark or complex spaces use 0.45. When IES photometry is active, this field is hidden and the estimator uses the selected workplane height, LLF, and simplified reflectance adjustment instead.
Photometry / Simulation Note: When usable IES photometry is available for the selected fixture, this estimator uses the fixture’s IES candela data, selected workplane height, light loss factor, and simplified reflectance adjustment to estimate fixture count, average foot-candles, and visual light distribution. The reflectance adjustment is a conservative approximation and is not a full zonal-cavity, radiosity, or professional photometric room calculation. When IES photometry is not available, the estimator uses a simulated beam model based on lumens, mounting height, room/layout condition, light loss factor, and beam angle.
Preliminary Estimate Only: This estimator is intended for simple square or rectangular spaces and should be used as a planning aid, not a final photometric lighting plan. Actual light levels may vary based on fixture optics, selected IES file, mounting conditions, workplane height, ceiling height, surface reflectance, obstructions, controls, voltage, installation conditions, and site-specific requirements. Project-critical applications should be verified with a formal lighting plan.
This estimate is a starting point. Warehouses, industrial facilities, hazardous locations, sports areas, schools, healthcare spaces, public areas, and code-sensitive projects may require a reviewed lighting layout before purchase or installation.
Product Overview
This adjustable round explosion proof LED light provides 40W, 60W, or 80W output settings with 6,400, 9,600, or 12,800 lumens. It is built for hazardous location lighting where its UL 844 hazardous location classifications match the project requirements.
The fixture operates on 100-277V and offers 4000K, 5000K, or 6500K color temperature selection. A 120-degree beam angle and tempered glass lens provide broad area illumination.
Core Performance and Output
At 160 lumens per watt, this fixture delivers up to 12,800 lumens while using up to 80W. It is identified as a replacement for 175W metal halide lighting.
1-10V dimming is supported. The fixture has a power factor greater than 0.95 and total harmonic distortion below 10%.
Longevity and Reliability
The LED system is rated for 50,000 L70 hours. The die-cast aluminum housing, tempered glass lens, IK08 impact rating, and 10kV surge protection support use in demanding industrial environments.
This fixture is IP66 rated, NEMA 4X rated, and operates from -40 degrees F to 131 degrees F. It is rated T4A at an ambient temperature of 55 degrees C and has a 3G vibration rating.
Build Quality and Physical Characteristics
The round gray fixture measures 11.22 x 10.39 inches and weighs 14.5 lb. Mounting options include surface, yoke, and 3/4 in NPT pendant mounting. No cord is included.
Where This Product Fits Best
This hazardous location fixture is suited to installations requiring Class I, II, or III hazardous location classifications and a compact round fixture with multiple mounting options.
- hazardous location lighting
- explosion proof lighting
- paint booth lighting
- chemical processing facility lighting
- oil and gas facility lighting
- refinery lighting
- marine environment lighting
- wastewater treatment lighting
Safety, Certifications, and Warranty
The fixture is UL 844 listed for Class I, Division 2, Groups A, B, C, and D; Class II, Division 1, Groups E, F, and G; Class II, Division 2, Groups F and G; and Class III locations. It is also UL 1598 suitable for wet locations, UL 1598A Marine Outside Type, ABS, NEMA 4X, and UL certified.
A 5-year warranty is included.
Frequently Asked Questions
Q: What mounting options are available for this explosion proof LED light?
A: This explosion proof LED light can be surface mounted, yoke mounted, or pendant mounted using a 3/4 in NPT connection.
Q: What hazardous location classifications does this fixture carry?
A: This fixture is UL 844 listed for Class I Division 2 Groups A, B, C, and D; Class II Division 1 Groups E, F, and G; Class II Division 2 Groups F and G; and Class III locations.
Web ID: 2727